Legionella testing: who must test, and how often?

The operator of a drinking water installation must have it tested for Legionella when three conditions are met together: a drinking water heater with a capacity of more than 400 litres, or more than 3 litres in a hot water pipe, showers or other aerosol-generating fixtures, and the water is supplied as part of a commercial or public activity. Single and two-family houses are exempt (Section 31 TrinkwV).

Taking a water sample at a valve

When does the testing obligation apply?

Section 31(1) of the Drinking Water Ordinance sets out the conditions. All of them must be met:

  1. Size of the hot water system. A storage-type drinking water heater or a central instantaneous drinking water heater with a capacity of more than 400 litres, or more than 3 litres in at least one drinking water pipe between the outlet of the drinking water heater and the point of use. The content of a circulation pipe does not count towards this.
  2. Aerosol formation. The system has showers or other fixtures in which the drinking water is dispersed into a fine mist.
  3. Not a single or two-family house. Systems in single and two-family houses are exempt.
  4. Commercial or public supply. The drinking water is supplied as part of a commercial or public activity.

The 2023 Ordinance no longer uses the former term "large-scale drinking water heating system" as a defined term in its own right; the criteria now appear directly in Section 31.

A positive result or action needed in your installation? Tell us the building, the result and the water volume. We will advise you on disinfecting the installation with chlorine dioxide and get back to you promptly.

Request advice Tel. +49-(0)5138-708 78 38 Dosing guide

How often must testing take place?

System and activityIntervalReference
Building, commercial activity (for example letting)at least every three yearsSection 31(2) No. 2(a)
Building, public activityat least once a yearSection 31(2) No. 2(b)
Building, public activity, after three years without findingsthe health authority may set an interval of up to three years; not for facilities under Section 23(5) of the German Infection Protection Act (IfSG), care facilities and facilities with at-risk patientsSection 31(3)
Mobile and temporary systemsfrequency is set by the health authoritySection 31(2) No. 1
Newly commissioned systemfirst test within three to twelve months of commissioningSection 31(4)

Under Section 2 No. 8, "commercial" means supply as part of letting or of any other independent, regular activity carried on for profit. Under Section 2 No. 9, "public" means supply to an indefinite, changing group of people who are not connected by personal relationships.

Who takes the samples?

Testing under the Drinking Water Ordinance, including sampling, may only be carried out by accredited laboratories (Section 39(1)). The operator commissions such a laboratory; the federal states publish lists of accredited laboratories (Section 40(2)). Samples must be taken at several representative points (Section 41(4)).

Where are the samples taken?

The German Environment Agency (UBA) recommendation on systemic testing, dated 13 October 2025, names three types of sampling point: the outlet of the hot water pipe at the drinking water heater, the point where the circulation pipe re-enters the drinking water heater, and outlets in the periphery connected, with as short a connecting pipe as possible, to the end of the risers. Sampling follows DIN EN ISO 19458, purpose b. More on this under Sampling and measurement.

Frequently asked questions about Legionella testing

As the landlord of a multi-family building, do I have to have testing done?

Yes, if the building meets the criteria in Section 31: a drinking water heater with more than 400 litres, or more than 3 litres in a hot water pipe, plus showers. Letting is a commercial activity, so testing is then due at least every three years.

Does the obligation also apply to single and two-family houses?

No. Section 31(1) No. 3 TrinkwV expressly exempts systems in single and two-family houses.

Does the circulation pipe count towards the 3 litres?

No. Under Section 31(1) No. 1 TrinkwV, the content of a circulation pipe is not taken into account. What matters is the content of the pipe between the outlet of the drinking water heater and the point of use.

Can the testing interval be extended?

Yes, for public activity: if the annual tests show no findings for three years in a row, the health authority may set an interval of up to three years. This does not apply to facilities under Section 23(5) of the German Infection Protection Act (IfSG), care facilities and facilities with patients at higher risk of infection.

When is the first test due for a new system?

Within three to twelve months of commissioning, under Section 31(4) TrinkwV.

What happens if testing finds Legionella?

From 100 CFU per 100 ml, the obligations under Section 51 apply: notification, establishing the cause, a risk assessment and measures. The steps in detail are set out under Positive Legionella result: what to do now.

Next step

A positive result or action needed in your installation? Tell us the building, the result and the water volume. We will advise you on disinfecting the installation with chlorine dioxide and get back to you promptly.

biostream® ZERO is a chlorine dioxide concentrate for drinking water, available in the shop in 250 ml, 1000 ml and 5 litres. We offer further container sizes as direct delivery, from 25-litre containers up to 20,000 litres (tanker truck). The dosing guide calculates the quantity for your system.

Request advice Tel. +49-(0)5138-708 78 38 Dosing guide biostream® ZERO

Sources

This page does not replace legal advice or information from the health authority. The version of the Drinking Water Ordinance in force at the time is authoritative.